Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2004 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
| 08/25/2004 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) DRAIN AND SEWER PIPES MUST CONTINOUSLY BEAR ON COMPACTED OR UNDISTURBED SOIL PRESENTLY BRIDGED NOT ALLOWED 2) DRAIN WASTE AND VENT SYSTEMS MUST BE TESTED WITH A 10 FOOT COLUMN OF WATER 3) BLDG FOOTERS MUST BE A MINIMUM OF 16" IN WIDTH 4) REINFORCING STEEL MUST BE AMINIMUM OF 3" ABOVE SOIL 5) EXISTING FOUNDATION MUST HAVE #4 REBAR PINS AT 24" ON CENTER 6) EXTEND SHOWER VENT OR SHORTEN DIRTY ARM LENGTH TO LESS THAN 60" TO VENT 7) WRAP ABS PLASTIC IN CONTACT WITH CONCRETE |