Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/08/2004 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection :* |
| 05/18/2004 |
ELECTRIC - INTERMEDIATE |
|
Partial Approval |
INSTA HOT TO BE INSTALLED? - NO DEDICATED CIRCUIT FOR THIS AND THERE IS A 2 POLE 30 AMP FOR A WTR HTR. PLEASE COMPLY WITH MIN. CODE REQIUREMENTS PRIOR TO FINAL. |
| 05/14/2004 |
ELECTRIC - INTERMEDIATE |
|
Denied |
BOXES NOT PLOUD PER PLAN. NEED TO SUPPORT M.C. CABLE PER MIN. CODE. NEED TO CENTER M.C. CABLE IN METAL 2X4 STUDS ( IF RUNNING CABLE IN INSIDE CHANNEL. |