Permit: T04CM02025

Parcel: 128100530

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
06/02/2004 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
06/01/2004 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*/ 1) WHERE ARE EXIT LIGHTS AS PER PLANS. 2) M/C TO BE SUPPORTED AS PER 334-10 AND 300-11. 3) LIGHT FIXTURE SUPPORT WIRE TO BE ON OPPISITE CORNERS. 4) SCREWS TO BE 4 AT CORNERS. 5) PLEASE REVISE PLANS AS TO RELOCATED FIXTURES.
05/28/2004 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) SUPPORT EMT WITHIN 3' EACH BOX AND AT 10' INTERVALS, IF SUPPORTED WITH #9 CEILING WIRE MUST BE INDEPENDANT OF GRID SUPPORT SYSTEM, AND MUST BE TIED OFF BOTH ENDS. 2) ABANDON UN-USED CONDUIT AND BOXES CABLING PLUG UNUSED KO'S.