Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM02025
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/02/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
06/01/2004 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :*/ 1) WHERE ARE EXIT LIGHTS AS PER PLANS. 2) M/C TO BE SUPPORTED AS PER 334-10 AND 300-11. 3) LIGHT FIXTURE SUPPORT WIRE TO BE ON OPPISITE CORNERS. 4) SCREWS TO BE 4 AT CORNERS. 5) PLEASE REVISE PLANS AS TO RELOCATED FIXTURES. | |
05/28/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) SUPPORT EMT WITHIN 3' EACH BOX AND AT 10' INTERVALS, IF SUPPORTED WITH #9 CEILING WIRE MUST BE INDEPENDANT OF GRID SUPPORT SYSTEM, AND MUST BE TIED OFF BOTH ENDS. 2) ABANDON UN-USED CONDUIT AND BOXES CABLING PLUG UNUSED KO'S. |