Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2005 | PLUMBING - YARD WTR LINE/TEST | Approved | ||
| 03/28/2005 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BACKFLOW PREVENTER REQUIES UNIONS. 2) SHALL EXPOSE WATER SUPPLY TO METER & BACKFLOW PREVENTER. |
|
| 02/28/2005 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) YARD WATER LINE IS OK FROM BLDG SERVICE TO METER LOCATION SHALL SEE FINAL CONNECTION TO METER. 2) BLDG SEWER WATER TEST OK, TWO WAY C.O. OK | |
| 02/24/2005 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SOIL WATER TEST IS OK. 2) NOTE: THIS INSPECTION IS FOR BLDG. SEWER FROM TWO WAY C.O TO 20' OF M.H. 3) SHALL PROVIDE A SWING JOINT FOR WATER LINE. |