Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2005 | PLUMBING - INTERMEDIATE | Approved | ||
| 02/10/2005 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SOIL WATER TEST IS OK. 2) OVERHEAD WATER DISTRIBUTION IS OK 3) OK FOR DRYWALL EXCEPT @MOP SINK. 4) THERE IS A KINK IN 1/2" H.W SUPPLY @MOP SINK AND PROVIDE A ISOLATOR. 5) NOTE: RED LINE APPROVED PLANSFOR C.W SUPPLY | |
| 02/03/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 3" SAN CROSS FOR RE VENT IS UPSIDE DOWN. 2) APPROVED PLANS CALL FOR 3/4" HOSE BIB @ FRONT OF BLDG. 3) SHALL PROVIDE APPROVED HANGERS FOR OVERHEAD WATER LINE TO HOSE BIB 4) INSTALL CLOSET RINGS. 5) SERVICE SHUT OFF VALVE SHOWS TO BE LOCATED IN CEILING. 6) SHALL PROVIDE WRAP FOR 1" C. W. BY DOOR THAT PENETRATES FLOOR. 7) RE TEST SOIL SYSTEM |
|
| 01/31/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ADDRESS BOARD UP 2) KEEP ACCESS INTO SITE OPEN. 3) IMPROPER TEST ON WATER LINES ( 50 PSI MIN) 4) INCOMPLETE WORK ON WASTE LINES. 5) 1" CU IMBEDDED IN CONCRETE WITHOUT PROPER WRAP JUST WEST OF NE DOOR |