Permit: T04CM02013

Parcel: 137313730

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
04/11/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/10/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :* OK WALLS & HARD LIDS EXCEPT WALL WHERE PANEL IS INSTALL PANEL & TERMINATE CABLES AND CALL FOR INSP.
02/03/2005 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :* NOT READY
02/01/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* NOTES: 1) MC CABLE TO BE SUPPORTED TO STRUCTURE, WITHIN 12" OF TERMINATION AND AT 6' INTERVALS, CABLE RUNNING THRU BANDING TO HOLD UP INSULATION NOT CONSIDERED SUPPORTED. SEE ART 330 NEC.
01/31/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* PERMIT MUST BE POSTED ON JOB SITE. PLANS MUST BE ON SITE.