Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/10/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS & HARD LIDS EXCEPT WALL WHERE PANEL IS INSTALL PANEL & TERMINATE CABLES AND CALL FOR INSP. | |
| 02/03/2005 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NOT READY | |
| 02/01/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* NOTES: 1) MC CABLE TO BE SUPPORTED TO STRUCTURE, WITHIN 12" OF TERMINATION AND AT 6' INTERVALS, CABLE RUNNING THRU BANDING TO HOLD UP INSULATION NOT CONSIDERED SUPPORTED. SEE ART 330 NEC. |
|
| 01/31/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* PERMIT MUST BE POSTED ON JOB SITE. PLANS MUST BE ON SITE. |