Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM01992
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/21/2004 | FRAMING | Approved | IVRS - Inspection :* | |
06/18/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) 5/D3 AND 3/D3 NOT COMPLIED WITH AT SHEAR WALL |
|
06/17/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SEE LAST INSPECTION 2) MECHANICAL NOT COMPLETE 3) CONDENSATE LINES NOT INSTALLED |
|
06/16/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) ANCHOR BOLT MISSING GARAGE EAST WALL 2) 5/D3 NOT COMPLIED WITH GARAGE #5 SHEARWALL 3) RED HEAD ANCHORS LOOSE 4) 1/2" CLEARANCE REQUIRED BETWEEN SCISSOR TRUSS AND NON BEARING WALL 5) SHEAR WALL STUD AT BACK OF HOUSE OVER NOTCHED 6) REAR SHEAR 7) HOSE BIB BENT 8) TUB VENT OUT OF WALL 9) PROVIDE ENGINEER APPROVED DETAIL FOR SHEARWALL TRANSFER BETWEEN DROP CEILING AND BOTTOM CHORD OF TRUSS AT DOUBLE #1 SHEARWALLS 10) FIRESTOP KITCHEN CHASE 11) NO DWV WATER TEST |