Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T04CM01987

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/04/2004 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
06/03/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ 1) SUPPORT MC CABLE AS PER CODE 334-10 AND 300-11 - EXIT LIGHTS. 2) ATTACH FIXTURE TO GRID 410-16. IF USING MNFG CLIPS THEY MUST BE EFFECTIVE. IF SCREWS, 4 ON CORNERS OR 2 ON CENTER.
05/27/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ 1) OK TO COVER MC DROPS ABOVE PANELS. 2) OK CEILING AREAS IN ROOMS CORRIDOR NEED EM. LIGHTS AND EXIT LIGHTS, REAR ENTRY NEEDS LIGHT RELOCATION.