Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T04CM01987
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
06/03/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) SUPPORT MC CABLE AS PER CODE 334-10 AND 300-11 - EXIT LIGHTS. 2) ATTACH FIXTURE TO GRID 410-16. IF USING MNFG CLIPS THEY MUST BE EFFECTIVE. IF SCREWS, 4 ON CORNERS OR 2 ON CENTER. | |
05/27/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ 1) OK TO COVER MC DROPS ABOVE PANELS. 2) OK CEILING AREAS IN ROOMS CORRIDOR NEED EM. LIGHTS AND EXIT LIGHTS, REAR ENTRY NEEDS LIGHT RELOCATION. |