Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T04CM01985
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
10/26/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) EXCESSIVE OVER CURRENT PROTECTION ON A/C. MAXIMUM ALLOWED 35 AMP, INSTALLED 50 AMP 2) OUTSIDE HOSE BIBS REQUIRE ANTI-SIPHON VALVES 2 EACH 3) WATER HEATER VENT CONNECTOR REQUIRES 1/4/FT PITCH AND 3 SCREWS AT "B" CONNECTION |