Permit: T04CM01985

Parcel: 136406510


Addresses:

2386 S ADVENTURE TR


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T04CM01985

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/27/2004 BUILDING - FINAL Approved IVRS - Inspection :*
10/26/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) EXCESSIVE OVER CURRENT PROTECTION ON A/C. MAXIMUM ALLOWED 35 AMP, INSTALLED 50 AMP 2) OUTSIDE HOSE BIBS REQUIRE ANTI-SIPHON VALVES 2 EACH 3) WATER HEATER VENT CONNECTOR REQUIRES 1/4/FT PITCH AND 3 SCREWS AT "B" CONNECTION