Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T04CM01968
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/09/2004 | ELECTRIC - TEMP POWER FOR TEST | Approved | 1) SECURE "SES" AS PER MANUFACTURER INSTRUCTIONS | |
| 09/08/2004 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :*/ 1) PROTECT CONDUCTORS AT FITTINGS OVER #4 CONDUCTORS 300.4 (F) 2) SUPPORT PULL BOX ABOVE SERVICE 3) DO NOT ENERGIZE PANELS UNTILL INSPECTED 4) OK TEMP POWER FOR TEST 5) RECEIVED LETTER FOR TORQUE 6) BOND REQUIRED |