Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T04CM01967
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/07/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/06/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) WASTE AND VENT IN WOMENS RESTROOM PHASE 1 WATER TEST OK 2) SUPPORT OVERHEAD CAST AT CORRECT INTERVALS 3) INSTALL CORRECT END OF LINE CLEANOUT ON ? WALL 3) H20 PIPING IN PHASE 1 WATER TEST OK | |
08/02/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) WATER TEST ON ACID WASTE AND VENT TO JUST ABOVE CEILING HEIGHT AT POINT OF PENETRATION THRU 2ND FLOOR FOR BIOLOGY ROOM AND CHEMISTRY ROOM OK 2) NEED TO SEE WATER TEST THRU ROOF 3) H20 PIPING WATER TEST THESE 2 ROOMS IN WALL OK 4) WASTE AND VENT WATER TEST THESE 2 ROOMS TO JUST ABOVE CEILING HEIGHT AT SAME LOCATION AS ACID VENT OK 5) IN WALL OK TO COVER 6) 1" DROP TO BELOW FLOOR TIES INTO EXISTING PIPING. THAT IS UNDER BLDG AND ON THE GROUND. THIS CLEARLY VIOLATES 94 UPC SECTION 1211.3 |