Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T04CM01967
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
10/04/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) GIVE ME 1 HR CEILING DESIGN PER FIRE RESISTANCE DIRECTORY FOR INSPECTION OF CEILING IN RESTROOM. PREVIOUS PLASTER CEILING HAS LARGE SECTIONS COMPLETELY MISSING THAT CAN NOT BE REPAIRED PER APPEAL TO D. MANN 2) FLEX DUCT USED INSIDE RATED CEILING ASSEMBLY 3) WATER CLOSETS IN HC SPACES REQUIRE 18" TO CENTER (+/- 3/4") 4) ADA SIGNAGE REQUIRED ON WOMEN'S ROOM |
|
08/20/2004 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* TEMP C/O WING 3 OK | |
08/06/2004 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :*/ 1) T.C.O. FOR WING 3 CLASSROOMS OK |