Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 07/18/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) RE-INSPECT 2) GARAGE STEEL POST NOT INSTALLED UNDER GLB 3) OK TO INSULATE 4) ALL AREAS EXCEPT GARAGE 5) RECALL WHEN CENTER POST INSTALLED |
|
| 07/15/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OVERSPAN SW3 BOTTOM FLOOR 2) BLOCK REGISTERS 3-SIDES 3) CUT WIRES ROMEX UPSTAIRS BATH 4) ROMEX UPSTAIRS N.E. BATH MUST TERMINATE IN APPROVED BOX 5) 3" CLEARANCE ALL CANS 6) INSULATE BEHIND TUB WALLS 7) SECURE ALL 90'S THROUGH 1ST FLOOR 8) BLOCK TUB WALLS 9) LOOSE ANCHORS IN GARAGE 10) 8-16D NAILS AT TOP PLATE OVER DRYER VENT 11) NP UPSTAIRS VENT PIPES 12) WASTE VENTS NOT FULL TO ROOF TOP 13) RESTRICTED FLEX DUCT UPSTAIRS BATH CHASE 14) NP PEX UPSTAIRS BATH BEDROOM SOUTH 15) ? N.W. BATH VENT PIPE |
|
| 07/13/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 07/06/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* COMPLETE STUCCO MESH PRIOR TO INTERMEDIATE INSPECTIONS |