Permit: T04CM01960

Parcel: 115020200

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
08/02/2005 FRAMING Approved IVRS - Inspection :*
07/18/2005 FRAMING Partial Approval IVRS - Inspection :*
1) RE-INSPECT
2) GARAGE STEEL POST NOT INSTALLED UNDER GLB
3) OK TO INSULATE
4) ALL AREAS EXCEPT GARAGE
5) RECALL WHEN CENTER POST INSTALLED
07/15/2005 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OVERSPAN SW3 BOTTOM FLOOR
2) BLOCK REGISTERS 3-SIDES
3) CUT WIRES ROMEX UPSTAIRS BATH
4) ROMEX UPSTAIRS N.E. BATH MUST TERMINATE IN APPROVED BOX
5) 3" CLEARANCE ALL CANS
6) INSULATE BEHIND TUB WALLS
7) SECURE ALL 90'S THROUGH 1ST FLOOR
8) BLOCK TUB WALLS
9) LOOSE ANCHORS IN GARAGE
10) 8-16D NAILS AT TOP PLATE OVER DRYER VENT
11) NP UPSTAIRS VENT PIPES
12) WASTE VENTS NOT FULL TO ROOF TOP
13) RESTRICTED FLEX DUCT UPSTAIRS BATH CHASE
14) NP PEX UPSTAIRS BATH BEDROOM SOUTH
15) ? N.W. BATH VENT PIPE
07/13/2005 FRAMING Not ready for Inspection IVRS - Inspection :*
07/06/2005 FRAMING Not ready for Inspection IVRS - Inspection :* COMPLETE STUCCO MESH PRIOR TO INTERMEDIATE INSPECTIONS