Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
06/01/2004 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
05/20/2004 ELECTRIC - UNDERGROUND Partial Approval 1) OK 1" AND 2-3/4" CONDUITS ARE PER PLAN 2) RIGID BEYOND 24" TO EMERGENCE FROM PVC. SCHD 40 IN BETWEEN RIGID TO PVC FITTING
05/19/2004 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ CONDUIT DEPTH TO BE 24" MIN FROM TOP OF CONDUIT TO FINISH GRADE. SEE ART 300-5 NEC.