Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2007 | BUILDING - FINAL | Approved | PER INSP COPY | |
| 05/01/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL CONDENSATE DRAIN A/C UNIT 2) PAINT EXPOSED PLUMBING VENTS ON ROOF 3) COVERED WITHOUT INSPECTION-UNCOVER AND RECALL 4) RANGE REQUIRES 50 AMP CIRCUIT 5) EXHAUST FAN BATH INOPERATIVE 6) MULTIPLE WIRE NUTS USED IN PANEL-SHOUD BE FULL RUN TO BREAKERS 7) HOT WIRES MAIN PANEL INCORRECTLY COLOR CODED 8) POST ADDRESS NUMBER ON HOUSE 9) NEED LADDER ACCESS TO INSPECT ROOF A/C UNIT-30 AMP BREAKERS ? 10) DRYER REQUIRES 4 WIRE SYSTEM 11) INSTALL ANTI-TIP RANGE 12) STOPPED INSPECTION |