Permit: T04CM01930

Parcel: 115152710

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
05/25/2007 BUILDING - FINAL Approved PER INSP COPY
05/01/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL CONDENSATE DRAIN A/C UNIT
2) PAINT EXPOSED PLUMBING VENTS ON ROOF
3) COVERED WITHOUT INSPECTION-UNCOVER AND RECALL
4) RANGE REQUIRES 50 AMP CIRCUIT
5) EXHAUST FAN BATH INOPERATIVE
6) MULTIPLE WIRE NUTS USED IN PANEL-SHOUD BE FULL RUN TO BREAKERS
7) HOT WIRES MAIN PANEL INCORRECTLY COLOR CODED
8) POST ADDRESS NUMBER ON HOUSE
9) NEED LADDER ACCESS TO INSPECT ROOF A/C UNIT-30 AMP BREAKERS ?
10) DRYER REQUIRES 4 WIRE SYSTEM
11) INSTALL ANTI-TIP RANGE
12) STOPPED INSPECTION