Permit: T04CM01930

Parcel: 115152710

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
10/24/2005 EXT METAL CLIPS/EXT SHEATHING Approved
09/27/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) KITCHEN LIGHTS NOT PER PLAN
2) FIREBLOCK ALL DROPPED CEILING AREAS
3) LIGHTS NOT INSTALLED CLOSETS
4) INSTALL DBL STRAPS PORCH BEAMS TO MASONRY
5) NAIL NOT DONE
6) MASTER BEDROOM DUCT TO BE IN CENTER OF ROOM
7) BLOCK 3 SIDES MECH VENTS AT CEILING
8) SECURE WASHER BOX BETTER
9) BLOCK AROUND TUB
10) MUST USE LONG SWEEPS PLUMBING VENTS
11) 50 AMP RANGE RECEPTACLES UNDERSIZED WIRES
12) NEED H20 TEST D.W.V. PIPING THRU ROOF
13) BEDROOM RECEPTACLE NOT PER PLAN
14) GROUND ALL METAL ELECTRIC BOXES
15) STRAP PLUMBING H20 LINES THROUGHOUT
16) CEILING FAN BOXES TO BE APPROVED FOR USE
17) PLAN SHOWS H20 HEATER OUTSIDE
18) CANNOT USE PVC FOR H20 HEATER PTR LINE
19) PLANS SHOWS HEAT PUMP OUTSIDE ON GROUND
20) BETWEEN MASONRY AND FRAME WALLS INSTALL FIRESTOP VERTICALLY (MAXIMUM 10' HORIZONTAL RUN)
21) INSTALL NAIL BANG PLATES PLUMBING ELECTRIC THROUGHOUT
22) MUST USE RIDGID DRYER DUCT
23) STOPPED INSPECTION
05/09/2005 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) MAIN HOUSE AND CARPORT OK FRONT ENTRY PORCH NOT READY
04/29/2005 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*