Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2005 | EXT METAL CLIPS/EXT SHEATHING | Approved | ||
| 09/27/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN LIGHTS NOT PER PLAN 2) FIREBLOCK ALL DROPPED CEILING AREAS 3) LIGHTS NOT INSTALLED CLOSETS 4) INSTALL DBL STRAPS PORCH BEAMS TO MASONRY 5) NAIL NOT DONE 6) MASTER BEDROOM DUCT TO BE IN CENTER OF ROOM 7) BLOCK 3 SIDES MECH VENTS AT CEILING 8) SECURE WASHER BOX BETTER 9) BLOCK AROUND TUB 10) MUST USE LONG SWEEPS PLUMBING VENTS 11) 50 AMP RANGE RECEPTACLES UNDERSIZED WIRES 12) NEED H20 TEST D.W.V. PIPING THRU ROOF 13) BEDROOM RECEPTACLE NOT PER PLAN 14) GROUND ALL METAL ELECTRIC BOXES 15) STRAP PLUMBING H20 LINES THROUGHOUT 16) CEILING FAN BOXES TO BE APPROVED FOR USE 17) PLAN SHOWS H20 HEATER OUTSIDE 18) CANNOT USE PVC FOR H20 HEATER PTR LINE 19) PLANS SHOWS HEAT PUMP OUTSIDE ON GROUND 20) BETWEEN MASONRY AND FRAME WALLS INSTALL FIRESTOP VERTICALLY (MAXIMUM 10' HORIZONTAL RUN) 21) INSTALL NAIL BANG PLATES PLUMBING ELECTRIC THROUGHOUT 22) MUST USE RIDGID DRYER DUCT 23) STOPPED INSPECTION |
|
| 05/09/2005 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) MAIN HOUSE AND CARPORT OK FRONT ENTRY PORCH NOT READY |
|
| 04/29/2005 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |