Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM01908
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/02/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/OK FOR FINAL C/O. OK BLDG. FINAL AS PER BOB SUBA | |
11/01/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/A/C 1 WIRE SIZE NOT ADEQUATE. BREAKER NOT ADEQUATE. CONNECT CONDENSATE FROM A/C 1 BELOW TEE. CONNECT COOLER DRAIN. PROVIDE AN APPROVED CAP ON WATER HEATER VENT. PROVIDE A DATA PLATE FOR CONDENSOR SHOWING PROPER FUSE REQUIREMENTS & PROVIDE INSTALL INSTRUCTIONS. DUCT SMOKE DETECTOR NOT WORKING |
|
10/04/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NEW A/C LABEL DATA PLATE WITH HEAT STRIP AND FUSE ACCORDINGLY 2) LABEL SUITE NUMBER ON ALL EQUIPMENT ON ROOF 3) PROVIDE ROOF JACKS AT ALL ROOF PENETRATIONS 4) EXTEND SEWER VENTS 2' ABOVE EVAP COOLER 5) PROVIDE CONDENSATE DRAIN ON A/C UNIT AND DRAIN ON COOLER 6) PROVIDE WATER TO THE EVAP COOLER 7) WATER HEATER VENT INSTALLED UPSIDE DOWN AND EXTEND TO ABOVE WALL 8) NEED TO TEST DUCT SMOKE DETECTORS 9) PROVIDE DISCONNECT ON CONDENSAOR ON ROOF-EXTEND SEWER VENT 2' ABOVE FRESH AIR INTAKE ON A/C UNIT 10) BE SURE EVAP COOLER IS INTERLOCKED WITH EXHAUST FAN 11) RECALL FOR INSPECTION |