Permit: T04CM01906

Parcel: 119420350


Addresses:

1809 W MISSION PL

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
08/03/2004 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
06/25/2004 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*/ 1) MAIN ADDITION OK TO POUR 2) PATIO NOT READY
06/23/2004 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*/ 1) PLAN CALLS FOR 2-#4 REBAR HORIZONTAL IN FTG. 2) OVERLAP #4 REBAR MINIMUM 30 BAR DIAMETER 3) ISOLATE REBAR DRIVEN INTO GROUND FROM HORIZONTAL STRUCTURAL REBAR 4) WORKING ON GAME ROOM-FTGS INCOMPLETE 5) PORCH NOT STARTED