Permit: T04CM01889

Parcel: 11310070B

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
05/28/2004 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*/ 1) corrections made ok. 2) abs dwv underground ok. 3) ok to cover.
05/27/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
05/24/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*/ 1) UNSUPPORTED PIPE, BACK PITCHED SECTIONS, AND SECTIONS WITH LESS THAN TWO PERCENT GRADE, ARE NOT PERMITTED 2) A TRAP ARM MUST BE AT LEAST TWO PIPE DIAMETERS IN LENGTH BETWEEN THE WEIR OF THE TRAP AND THE POINT OF VENT. SEE 1002.2 94 UPC