Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2005 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :*OK TO CLEAR C.D ONLY | |
| 01/21/2005 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED A GROUND BUSHING ON 2 1/2" CONDUIT COMING INTO BOTTOM OF SERVICE BECAUSE OF ENTRY THUR CONCENTRIC KNOCKOUTS 250-94 2) GROUND RODS HAVE TO BE #1 DRIVEN STRAIGHT DOWN #2 45% OR #3 FLAT & BURIED AT 2/1/2" DEEP THEY CANNOT BE BENT. |