Permit: T04CM01889

Parcel: 11310070B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/06/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/14/2004 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)PLAN SHOWS PANELS TO BE OUTSIDE BY SERVICE 2)SUB PANEL CONNOT BE IN A CLOSET, 99 NEC 240-24 D. STATES OVER CURRENT DEVICES SHALL NOT BE LOCATED IN THE VICINITY OF EASILY IGNITIBLE MATERIAL, DO NOT KNOW WHAT WILL BE STORED IN CLOSET. 3)110-26 OF THE 99 NEC A-2 STATES THE WIDTH OF THE WORKING SPACE IN FRONT OF THE PANEL SHALL BE EITHER THE WIDTH OF THE PANEL OR 30 INCHES--WHICH EVER IS GREATER, MEANING 30"S 4)EXHAUST FANS IN UTILITY CLOSETS MISSING 5)BATH ROOM EXHAUST FLANG IN WEST UNIT REQUIRE A COUNECTOR WHICH HOLDS ROMEX TO ENCLOSURE SUCH AS ROMEX CONNECTORS OR PLASTIC CONNECTORS SUCH AS ONES USED ON EAST UNIT.