Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/14/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/1)PLAN SHOWS PANELS TO BE OUTSIDE BY SERVICE 2)SUB PANEL CONNOT BE IN A CLOSET, 99 NEC 240-24 D. STATES OVER CURRENT DEVICES SHALL NOT BE LOCATED IN THE VICINITY OF EASILY IGNITIBLE MATERIAL, DO NOT KNOW WHAT WILL BE STORED IN CLOSET. 3)110-26 OF THE 99 NEC A-2 STATES THE WIDTH OF THE WORKING SPACE IN FRONT OF THE PANEL SHALL BE EITHER THE WIDTH OF THE PANEL OR 30 INCHES--WHICH EVER IS GREATER, MEANING 30"S 4)EXHAUST FANS IN UTILITY CLOSETS MISSING 5)BATH ROOM EXHAUST FLANG IN WEST UNIT REQUIRE A COUNECTOR WHICH HOLDS ROMEX TO ENCLOSURE SUCH AS ROMEX CONNECTORS OR PLASTIC CONNECTORS SUCH AS ONES USED ON EAST UNIT. |