Permit: T04CM01881

Parcel: 141012020


Addresses:

5330 S CIVANO BL


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T04CM01881

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/24/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*/ CORRECTION MADE. WASTE VENT AND WTR TEST THRU ROOF OK. H20 WTR TEST OK.
06/23/2004 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1)WASTE AND VENT WTR TEST TO BE THRU ROOF. 2) SUPPORT ALL PIPING AT APPROPRIATE INTERVALS WITH APPROVED METHODS. 3) PROVIDE SEPERATION ON HOT AND COLD PEX TUBING. 4) WHERE IS YOUR KITCHEN SINK DRAIN. 5) INSTALL PER PLAN. THIS MAY NOT BE A COMPLETE LIST. HAVE YOUR PLBR PRESENT AT TIME OF NEXT INSP.
06/18/2004 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) MUST USE DIRECTIONAL FITTING FOR FLAT VENT AT WTR CLOSET. 2) RETEST SYSTEM.