Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM01875
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2004 | MECHANICAL - FINAL | Approved | ||
| 09/29/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/PROVIDE LEGIBLE DATA LABELS FOR FAN COILS. MARK FAN COILS W/PROPER HEAT STRIP & BE SURE TO FUSE DISCONNECTS ACCORDINGLY. WHITE WIRE CANNOT BE USED FOR LINE VOLTAGE. RECALL FOR INSPECTION |
|
| 09/24/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/PROVIDE TRAPS ON SECONDARY DRAINS. MAKE NECESSARY CORRECTIONS FROM PREVIOUS INSPECTION. |
|
| 08/09/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PROVIDE SECONDARY DRAINS ON FAN COILS 2) LABEL FAN COILS WITH UNIT NUMBER 3) PROVIDE BUSHINGS WHERE REFER LINES ENTER CABINET OF FAN COIL 4) REMOVE PAINT FROM DATA PLATES ON FAN COILS 5) NEED TO SEE CONDENSORS 6) OK TEMP C OF O PHASE 2 7) RECALL FOR INSPECTION |
|
| 07/01/2004 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :*/ OK FOR TEMP C OF O IN PHASE 1. |