Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04CM01875

Parcel: 12111162C


Addresses:

1636 N SWAN RD #103

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
09/30/2004 MECHANICAL - INTERMEDIATE Approved
05/24/2004 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*/ NORTH SIDE - PROVIDE SECONDARY DRAINS ON FAN COILS. TERMINATE IN A CONSPICUOUS LOCATION. SEAL ALL JOINTS AND CONNECTIONS ON DUCTING. BE SURE TO STRAP FLEX DUCT UP OFF OF GRID AND LIGHTS. OK FOR SHEET ROCK.