Permit: T04CM01875

Parcel: 12111162C


Addresses:

1636 N SWAN RD #103


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM01875

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/29/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ 1) RECEIVED LETTER FOR LIGHTING 2) OK FINAL
09/27/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1)
09/24/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) SUPPORT WIRES NEEDED FOR CANS 2) ELECTRICAL SUPPORT WIRE TO BE AS PER 300.11 3) TIGHTEN FIXTURE FITTINGS 4) SUPPORT M/C CABLE AS CODE 12" FROM BOX AND 6' SPACING 5) PLANS CALL FOR 277V LIGHTING 6) RECEIVED LETTER FOR DELETED OUTLETS 7) MAINTAIN WORKING CLEARANCES AT PANELS 110.26 8) FILL UNUSED OPENING IN PANEL 9) PLEASE REVISE PANEL SCHEDULES
08/09/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/06/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
07/02/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
07/01/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*