Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/29/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :*/ 1) RECEIVED LETTER FOR LIGHTING 2) OK FINAL |
| 09/27/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) |
| 09/24/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) SUPPORT WIRES NEEDED FOR CANS 2) ELECTRICAL SUPPORT WIRE TO BE AS PER 300.11 3) TIGHTEN FIXTURE FITTINGS 4) SUPPORT M/C CABLE AS CODE 12" FROM BOX AND 6' SPACING 5) PLANS CALL FOR 277V LIGHTING 6) RECEIVED LETTER FOR DELETED OUTLETS 7) MAINTAIN WORKING CLEARANCES AT PANELS 110.26 8) FILL UNUSED OPENING IN PANEL 9) PLEASE REVISE PANEL SCHEDULES |
| 08/09/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |
| 08/06/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 07/02/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* |
| 07/01/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* |