Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/04/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHOWER NOT COMPLETE 2) PLASTIC FEMALE FITTINGS NOT ALLOWED WITH METAL MALE FITTINGS AT SHOWER 3) DBL LAV NOT PLUMBED OR VENTED 4) BALL VALVES CANNOT BE ENCLOSED IN WALL WITHOUT ACCESS PANEL 6) CLIP TRUSS NORTH END TO BEARING WALL WITH H2.5 CLIPS 7) ALL WIRES MUST TERMINATE IN APPROVED ELECTRIC BOXES 8) ANCHOR BOLTS REQUIRED WITHIN 12" OF BOTTOM PLATE SPLICES 9) SMOKE DETECTOR REQUIRED WITHIN 12" OF BEDROOM CEILING AND IN HALL 10) CLIP TRUSSES AT MID POINT BEARING 11) WATER HEATER "B" VENT NOT INSTALLED |
|
| 11/01/2004 | FRAMING | Not ready for Inspection | IVRS - Inspection :*/ 1) NEED STUCCO MESH COMPLETED BEFORE INTERMEDIATES | |
| 10/28/2004 | FRAMING | Not ready for Inspection | IVRS - Inspection :*/ 1) INTERMEDIATE INSPECTIONS ARE NOT PERFORMED UNTIL THE STUCCO MESH IS COMPLETE | |