Permit: T04CM01852

Parcel: 141014710

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T04CM01852

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/15/2004 BUILDING - FINAL Approved IVRS - Inspection :*
09/13/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) NO FUSES IN A/C DISCONNECT BOXES ( EAST AND WEST) 2) PROVIDE PROPER ACCESS CLEARANCE TO A/C DISCONNECT AROUND EXTERIOR COMPONENT ON WEST SIDE 3) CORRECT DIFFERENT GAUGE GROUND WIRES DBL TAPPED IN PANEL 4) PANEL SPECS DO NOT PROVIDE FOR DBLE TAPPING NEUTRALS 5) NEED 2ND SCREW FOR PANEL DEAD FRONT 6) FURNACE INSTALL NOT COMPLETE 7) RAISE DISHWASHER DRAIN TO COUNTER BOTTOM