Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T04CM01852

Parcel: 141014710

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
09/15/2004 BUILDING - FINAL Approved IVRS - Inspection :*
09/13/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) NO FUSES IN A/C DISCONNECT BOXES ( EAST AND WEST) 2) PROVIDE PROPER ACCESS CLEARANCE TO A/C DISCONNECT AROUND EXTERIOR COMPONENT ON WEST SIDE 3) CORRECT DIFFERENT GAUGE GROUND WIRES DBL TAPPED IN PANEL 4) PANEL SPECS DO NOT PROVIDE FOR DBLE TAPPING NEUTRALS 5) NEED 2ND SCREW FOR PANEL DEAD FRONT 6) FURNACE INSTALL NOT COMPLETE 7) RAISE DISHWASHER DRAIN TO COUNTER BOTTOM