Permit: T04CM01848

Parcel: 12709012C

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
07/14/2004 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
07/12/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ 1) OK M/C AND FLEX SUPPORTING OF CABLES 2) FINISH PREVIOUS ITEMS
07/09/2004 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*/ 1) SUPPORT FIRE ALARM AND V CABLES UP OFF OF GRID 2) SUPPORT M/C CABLE AND FLEX CONDUITS AS PER CODES AND 300-11 3) FINISH MAKE UP AND GROUND BOXES 4) OK 2 X 4 LAYING
06/28/2004 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*/ ANSWERED QUESTION FOR CODE RELATED TO EXISTING WIRING.