Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T04CM01821
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/12/2004 | BUILDING - FINAL | Approved | IVRS - Inspection :*/ 1) RE-INSPECT | |
11/02/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GAS LINE NOT HOOKED UP TO FAU 2) PAN FULL OF BLOWN INSULATION |
|
10/18/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950*/ 1) REMOVE PAINT FROM GAS LINE TO PROVIDE ELECTRIC BOND 2) NO POST TENSION TAG ON WATER SERVICE 3) HANDY CAP WALK HAS 4 FOOT DROP OFF. PROVIDE GUARD RAIL 4) WATER HEATER "B" VENT PLUGGED WITH TAPE AND MISSING SCREWS 5) FURNACE GAS NOT CONNECTED 6) PAGE 24 OF FURNACE MANUAL NOT COMPLIED WITH 7) STOPPED INSPECTION |