Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T04CM01812
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/12/2004 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
05/25/2004 | MECHANICAL - ABOVE CEILING | Partial Approval | SHEET M-1 INDICATES TWO TRANSFER PENETRATIONS THAT HAVE BEEN BLOCKED. IS THIS CORRECT? IF SO, PROVIDE DRAWING FROM ARCH SHOWING HOW AIR IS TRANSFERRING OTHERWISE. IF INCORRECT, WALLS ARE RATED OR OTHERWISE FIRE DAMPERS MAY BE NEEDED. EITHER OPEN THESE PENETRATIONS BACK UP OR REDRAW PLAN SHOWING ACCURATE DESCRIPTION OF AIR TRANSFER PRIOR TO FINAL. |