Permit: T04CM01812

Parcel: 10511061R

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T04CM01812

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
11/12/2004 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
05/25/2004 MECHANICAL - ABOVE CEILING Partial Approval SHEET M-1 INDICATES TWO TRANSFER PENETRATIONS THAT HAVE BEEN BLOCKED. IS THIS CORRECT? IF SO, PROVIDE DRAWING FROM ARCH SHOWING HOW AIR IS TRANSFERRING OTHERWISE. IF INCORRECT, WALLS ARE RATED OR OTHERWISE FIRE DAMPERS MAY BE NEEDED. EITHER OPEN THESE PENETRATIONS BACK UP OR REDRAW PLAN SHOWING ACCURATE DESCRIPTION OF AIR TRANSFER PRIOR TO FINAL.