Inspection History: ELECTRIC - FINAL

Permit Number - T04CM01812

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/10/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/04/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ RECEIVED CHECK #44339527 FOR AFTER HOURS INSP. $108.00. 1) PLAN REVISION STILL NEEDED - CIRCUITS TO PANEL SCHEDULE, GROUNDING EQUIPMENT CONDUCTOR IS #8 PLANS CALL #6, CODE IS #10, MAIN IS A BREAKER NOT DISCONNECT. 2) ANOTHER WORKING CLEARANCE IN FRONT OF ELECTRICAL EQUIP. 110-26. OK TEMP C OF O TO OPEN.
06/03/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ OK TRACK LIVE END. ELECTRIC IN WALL IS NOW EXPOSED FOR USE - OK TO CLOSE. CORDS NOT TO PASS THRU CABINET CONCEALED.
06/01/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) WORK IS NOT REFLECTIVE OF PLANS. PLEASE REVISE PLANS OR INSTALL AS PER PLANS - SERVICE 1 - LINE, PANEL SCHEDULE, LIGHTING CONDUCTOR. 2) TRACK POWER FEED TO BE ACCESSABLE. 3) CORDS NOT TO PASS THROUGH WALLS OR CABINET WALLS, 400-7, 400-8, ELECTRIC TO BE ACCESSABLE.