Permit: T04CM01803

Parcel: 10604252D

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T04CM01803

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
07/01/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*/ CORRECTIONS MADE OK. 2) OK TO COVER ALL AREAS.
06/30/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
06/29/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) NEED TO SEE WTR TEST ON ABS NEED TO SEE CLOSET FLANGES. 2) COPPER WTR PIPING OK. PRESSURE TEST OK. 3) A TRAP ARM MAY NOT CHANGE SIZE - GRADE IS TO BE 2% PERIOD. 4) HANGERS REQUIRED AT END OF BRANCHES, CHANGES OF DIRECTION AND CHANGES OF ELEVATION. 5) OK TO COVER SUBJECT TO WTR TEST.