Permit: T04CM01796

Parcel: 111072930


Addresses:

3108 E TOWNER ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
07/08/2004 BUILDING - FINAL Approved IVRS - Inspection :*
07/07/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) ELECTRIC SERVICE PANEL BOTH GROUND WIRES ON SAME LUG MUST BE SAME SIZE AND SOLID AND STRANDED WIRES CANNOT BE ON SAME GROUND LUG 2) NO ONE HOME, NO ACCESS TO CHECK BATHROOM GFCI
06/28/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) BATH GFI WON'T RESET 2) DIFFERENT SIZE GROUND WIRE IN MAIN PANEL ARE DOUBLE TAPPED