Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/30/2004 | MECHANICAL - PROGRESS | Approved | ||
| 08/24/2004 | MECHANICAL - PROGRESS | Denied | IVRS - Inspection : See detailed listing on site.| 999*/DENIED 1)LABEL FAN COILS & CONDENSORS W/UNIT NUMBER 2)SUPPORT CONDENSATE DRAIN LINES 3)MARK UNIT DATA PLATES W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY. 4)DO NOT USE WHITE WIRE FOR LINE VOLTAGE 5) VENT ON CONDENSATE CHAINS MUST BE DOWNSTREAM OF THE TRAP 6)PROVIDE A CATWALK TO FAN COILS 7)PROVIDE A LIGHT & SERVICE RECEPTACLE AT EACH FAN COIL. 8) SEAL WHERE REFER LINES EXIT SIDEWALL OF ATTIC. 9)COMPLETE CONDENSATE DRAIN TERMINATION TO LAV. TAILPIECE. |