Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM01779
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/22/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/ C OF O. OK. | |
06/18/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ OK CORRECTIONS EXCEPT WHEN CONTR. INSTALLED NEW COVER PLATE HE DID NOT RE-LABEL THE CIRCUIT BREAKERS. |
|
06/14/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) FEEDER CONDUIT MUST BE SUPPORTED WITHIN 3' OF TERMINATION AT J-BOX BETWEEN TRNG ROOM AND SES. 2) USE PROPER COVER BETWEEN NEW BREAKERS AT SES INSTALLED COVER IS TO SHORT AND IS FASTENED WITH ONLY 1 SCREW. 3) CONDUIT SUPPORT IN WELDING SHOP NOT TO BE SUPPORTED UTILIZING OTHER TRADES PIPING. SUPPORT TO STRUCTURE - FEEDER. |
|
06/10/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) SUPPORT FEEDER CONDUIT WITHIN 3' EACH TERMINATION AT J-BOXES AND AT 10' INTERVALS - WELDING SHOP. 2) INSTALL MISSING COVER SECTIONS AT SES. 3) INSTALL GROUND WIRE IN RACEWAY FOR X-FORMER ABOVE TRNG ROOM. |