Permit: T04CM01779

Parcel: 13220003A


Addresses:

3401 E GAS RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM01779

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/22/2004 ELECTRIC - FINAL Approved IVRS - Inspection :*/ C OF O. OK.
06/18/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ OK CORRECTIONS EXCEPT WHEN CONTR. INSTALLED NEW COVER PLATE HE DID NOT RE-LABEL THE CIRCUIT BREAKERS.
06/14/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/ 1) FEEDER CONDUIT MUST BE SUPPORTED WITHIN 3' OF TERMINATION AT J-BOX BETWEEN TRNG ROOM AND SES. 2) USE PROPER COVER BETWEEN NEW BREAKERS AT SES INSTALLED COVER IS TO SHORT AND IS FASTENED WITH ONLY 1 SCREW. 3) CONDUIT SUPPORT IN WELDING SHOP NOT TO BE SUPPORTED UTILIZING OTHER TRADES PIPING. SUPPORT TO STRUCTURE - FEEDER.
06/10/2004 ELECTRIC - FINAL Denied IVRS - Inspection :