Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/30/2004 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :$ | |
| 04/28/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/26/2004 | MECHANICAL - FINAL | Partial Approval | CORRECTIONS REQUIRED: 1) NEED ACCESS INSIDE OF HOUSE TO CHECK RETURN AIR DUCTING. 2) GAS LINE, PRESS TEST, 14 PSI, OK. ON ROOF AT UNIT, NEED LONGES NIPPLE AT UNIT. FLARE NUT ON FLEX GAS LINE IN GASKET ON UNIT CASING. 3) CONDENSATE PIPING, DRAIN LINE IS IN DOWNSPOUT - AT REAR OF HOUSE - DRAINING ONTO SIDEWALK. THIS IS A DANGEROUS HAZARD. RE-RUN TO ACCEPTABLE TERMINATION. |