Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T04CM01655
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/28/2004 | PLUMBING - FINAL | Approved | IVRS - Inspection :*/ 1) CORRECTIONS MADE OK. 2) OK FOR C OF O PENDING ANY OTHER INSP. | |
06/25/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
06/24/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) SEE NOTE # 1 FROM 6/11/04. 2) SEE CODED NOTE #2 ON P-1 WTR HTR DIAGRAM. 3) SEE CODED NOTES #6 AND 7 ON P-1 WTR HTR DIAGRAM. 4) IN KENNEL - A TRAP ARM MAY NOT CHANGE SIZE. THE TRAP IS TO BE THE SAME SIZE AS THE TRAP ARM 1003.3 94 UPC. 5) IN AQUARIUM - A TRAP ARM IS TO BE INSTALLED AT 2%. SEE TABLE 10-1 94 UPC. 6) REQUIRE 12" CLEARANCE IN FRONT OF C.O. 707.10 94 UPC. 7) MAY NOT HAVE THREADED C.O. IN INACCESSABLE LOCATION 316.1.5 IS -5 94 UPC. INSPECTION STOPPED. | |
06/11/2004 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) CALL IN ALL REQUIRED INSPECTIONS BEFORE CALLING FINAL 2) PERMIT AND INSPECTION HISTORY TO BE ON JOB SITE AT ALL TIMES |