Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04CM01652

Parcel: 11611005H


Addresses:

2800 W BROADWAY BL


Inspection Status: Partial Approval

Inspection History: PLUMBING - SEWER HCS CONNECT

Permit Number - T04CM01652

Inspection Description - PLUMBING - SEWER HCS CONNECT

Inspection Status - Partial Approval

Date Description Inspector Results Comments
01/14/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/MANHOLE #6 -15 SECOND VACUUM TEST OK MANHOLE #5 -15 SECOND VACUUM TEST OK MANHOLE #15A -12 SECOND VACUUM TEST OK MANHOLE 16 - 48" X 36" MANHOLE - 6 SECOND VACUUM TEST OK MANHOLE #2 - 20 SECOND VACUUM TEST OK MANHOLE #1 -20 SECOND VACUUM TEST OK
01/13/2005 PLUMBING - SEWER HCS CONNECT Partial Approval # 7 MANHOLE 16 SECOND VACUUM TEST OK #17 MANHOLE 20 SEC VACUUM TEST OK #14 MANHOLE 15 SEC VAC TEST OK #15 MANHOLE 15 SEC VAC TEST OK #3 MANHOLE 20 SEC VAC TEST OK IVRS - Inspection :*
01/12/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*
1) #5 AIR TEST FROM MANHOLE #2 TO M.H. #3-OK
2) #5 AIR TEST FROM MANHOLE #2 TO M.H. #1-OK
3) #5 AIR TEST FROM MANHOLE #1 TO PUBLIC MANHOLE-OK
01/11/2005 PLUMBING - SEWER HCS CONNECT Partial Approval 1) 5# AIR TEST FROM M. H 15-A #5 -OK 2) # 5 AIR TEST FROM M. H 15-A TO # 16-OK 3) 5# AIR TEST FROM C.O #1 TO M.H #16 OK
01/07/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/1)5# AIR TEST BETWEEN MH #4 & #5, INCLUDING BBRANCH FOR CABANA, AND TWO BRANCHES FOR BLDG#3 OK 2)5# AIR TEST BETWEEN #6 & #5 OK 3)5# AIR TEST BETWEEN #6 & #7 OK 4)THESE TESTS INCLUDE BRANCH PIPING TO BLDGS. OK TO RECONNECT SEWER AT TWO WAY CLEAN-OUT. OK TO COVER.
01/07/2005 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/1)5# AIR TEST FROM MH #14 TO #7 OK
5# AIR TEST FROM MH #14 TO #15 OK 5# AIR TEST FROM MH #17 TO #6 OK 5# AIR TEST FROM MH #17 TO END OF LINE CLEAN-OUT OK
01/03/2005 PLUMBING - SEWER HCS CONNECT Not ready for Inspection IVRS - Inspection :* NOT READY
12/30/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/MANHOLE #12-15 + SECONDS VACUUM TEST OK. MANHOLE #13-15 + SECONDS VACUUM TEST OK
12/23/2004 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*/FROM 12/17/04
MANHOLE #11 48"X8' 20 SECOND VACUUM TEST OK
MANHOLE #10 48"X8.5' 15 SECOND VACUUM TEST OK
MANHOLE #9 48"X8.5' 20 SECOND VACUUM TEST OK
MANHOLE #8 48"X9' 20 SECOND VACUUM TEST OK
MANHOLE #7 48"X9' 20 SECOND VACUUM TEST OK 12/23/04
1)5# AIR TEST FROM MANHOLE #12 TO MANHOLE #11 OK
2)5# SIR TEST FROM #12 TO #13 OK
3)5# AIR TEST FROM #10 TO #11 OK
4)5# AIR TEST FROM #9 TO #10 OK
5)5# AIR TEST FROM #9 TO #8 OK
6)5# AIR TEST FROM #8 TO #4 OK