Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/22/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) SUPPORT ROMEX IN ATTIC PER N.E.C., BECAUSE ATTIC MUST BE ACCESSIBLE FOR J-BOXES 2) ROMEX MUST BE SUPPORTED WITHIN REASON TO PREVENT TRIP HAZARDS 3) EMT CONDUIT MUST HAVE BUSHED CONNECTORS AT ENDS IN ATTIC TO PREVENT CABLE FROM ABRAISON PER N.E.C. | |
| 09/13/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection :The wiring is not complete or does not comply with code.| COULD NOT LOCATE KEY TO APT, TRIED TO PAGE OWNER, NO CALL BACK 2 GROUND RODS REQUIRED, GROUNDING ELECTRODE CONDUCTOR TO BE TERMINATED IN MAIN DISCONNECTS FOR EACH UNIT, ALSO MUST BE BONDED TO GAS & WATER PIPING COVERS TO DISCONNECTS AT APARTMENTS MUST OPEN, BOLTS AT TOP HUB TOO LONG TO ALLOW COVER TO OPEN RECALL APTS TO BE NUMBERED FOR IDENTIFICATION ABOVE THE ENTRY DOORS |