Permit: T04CM01649

Parcel: 120082630


Addresses:

4757 S 7TH AV #01

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
08/10/2004 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
05/13/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*/ WHERE CONDUIT CANNOT MEET CONDITIONS FOR BURIEL DEPTH PER 300-5, A CONCRETE CAP OVER THE CONDUITS OF AT LEAST 2" OR MORE THICKNESS WILL BE APPROVED. OK TO BURY TRENCH EXCEPT OVER SHALLOW AREA. RE-CALL INSP WHEN CONCRETE POURED.