Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 02/13/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MOVE BLUE PEX LINE ABOVE LADDER 12" FROM CAN LIGHT 2) FURNACE B-VENT NEEDS 1" CLEAR TO COMBUSTIBLES (TOP 2 X 4) |
|
| 01/25/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CHECK FOR NAIL STOPS THRU-OUT 2) MOVE LOCATION OF WASHER AND DRYER RECEPTACLES 3) NEED 12" CLEARANCE PEX TO CAN LIGHT 4) RAISE WASHER BOX 5) NEED 1" CLEARANCE TO FURNACE B-VENT |