Inspection History Details
Inspection Status: Approved
Inspection History: ROOF NAILING
Permit Number - T04CM01619
Inspection Description - ROOF NAILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/06/2006 | ROOF NAILING | Approved | IVRS - Inspection :* | |
06/02/2006 | ROOF NAILING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER PAPERWORK TURNED IN BY INSPECTOR R. CAMACHO |
|
05/30/2006 | ROOF NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MANY LOOSE SHEETS THROUGHOUT 2) SHEETS NOT SPANNING 2 BAYS MUST BE BLOCKED AND NAILED OR REPLACED 3) STOPPED INSPECTION |
|
03/16/2006 | ROOF NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PER TRUSS CALC'S THIA26 HANGERS REQUIRED DBL GIRDER JACK TRUSS CONNECTION A06 TO X6 2) NAIL EVERY HOLE H.25 3) ALL 2 POINT BEARING TRUSSES REQUIRE 1/2" CLEARANCE FOR DEFLECTION INTERIOR WALLS 4) MANY LOOSE SHEETS 5) NAIL ALL EDGES AND FIELD PROPERLY-ROOF PANELS MUST SPAN 3 TRUSSES OR 2 BAYS ------------------------------------------------------------------------------------------------- 1) MISSING EXTERIOR GFI 2) EXTERIOR LIGHT FIXTURE MISSING ENTRY DOOR 3) PIG TAIL GROUND SWITCHES BEDROOM 3 4) PIG TAIL ALL GROUNDS IN SWITCH BOXES THROUGHOUT 5) PROVIDE COPPER BOND 6) BLOCK REGISTER BOOTS 3 SIDES 7) STOPPED INSPECTION |
|
12/12/2005 | ROOF NAILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SAFE ACCESS TO ROOF 2) FRAMING TO BE INSPECTED AT INTERMEDIATES |