Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/02/2005 | ELECTRIC - FINAL | Approved | ||
| 01/24/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PARTIAL CLEARANCE SUBJECT TO ITEM #2 SUBMIT LETTER OF TORQUE ON SW GEAR AND TERMINATIONS | |
| 01/20/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : 1) ADDRESS SERVICE OUTSIDE. 2) ?? OF TORQUE ON SWITCHGEAR TERMINATIONS AND PUTTING OF GEAR TOGETHER. 3) CANNOT LOCATE GAS BOND AS STATED ON PLAN 4/0 COPPER. 4) STRAP WATER BOND INSIDE BLD. 5) #2 BARE SOLID IN POLE BASES CANNOT WRAP AROUND NUT. |