Permit: T04CM01612

Parcel: 117110990


Addresses:

48 E PENNINGTON ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM01612

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/23/2004 ELECTRIC - FINAL Approved OK BY PHONE
09/16/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) TEMP GEN. POWER INSTALLATION IN PROGRESS. WIRE, PIPE AND CONNECTION/TERMINATIONS-OK
09/15/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ 1) NEED TO TIE IN GENERATOR 2) TALKED TO JOHN FIELDS OF YARBOROUGH CONST-WANTED TEMP C OF O WHICH WAS ALREADY GIVEN TO HIM BY M. CAPISTRAN ON 9/3/04
09/03/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) OK FOR TEMP C OF O. TEMP POWER VIA GENERATOR PENDING TEP UPGRADED FACILITY
09/02/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/TEMP C OF O NOT READY
1)CANNOT USE SCH 40 PUC ABOVE GROUND UNPRPTECTED
2)PLAN CALLS FOR PARALLEL FEEDS FROM GENERATOR TO SW GEAR
3)PENETRATIONINTO SW GEAR FROM GENERATOR CANNOT BE INTO A FRONT DEMOVEABLE? PANEL