Permit: T04CM01606

Parcel: 12713051B


Addresses:

5919 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Date Description Inspector Results Comments
10/28/2004 ELECTRIC - UNDERGROUND Approved
09/15/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*/ 1) OK TO TILE ROOM #106, 107 EXCEPT AS NOTED 2) OK POLE BASE 3) TIGHTEN LOOSE FITTINGS 4) JUNCTION BOXES TO BE BONDED 250-148 5) INSTALL CONDUIT-BOX SUPPORTS AS PER MANUFACTURERS INSTALLATION 6) LEAVE JUNCTION BOX TILES OPEN TO CHECK AFTER WIRE PULLED 7) CHECK ON 4 M FIXTURE/TRACK DETAIL 8) PVC CONDUIT PAST POLE IN BACK TO BE 24" UNDER PAVEMENT
09/03/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*/OK 4" PVC CONDUIT OUT FROM LAST INSPECTION
08/31/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*/PARTIAL-OK 2- 4" PVC PRIMARY OUT 50'
08/26/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*/ 1) POLE BASES OK TO COVER
08/25/2004 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*/ 1) CONDUITS TO BE AS PER 300.5 2) PLEASE MARK ASBUILT ON PLAN TO HIGHLIGHT WHEN COMPLETED RUNS
06/24/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*/ OK THREE 3/4" , ONE 1", TWO 1½" PVC SERVICE TO WALL. OK ONE 2½" , ONE 2" PVC SERVICE TO PANELS.