Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 03/02/2005 |
FRAMING |
|
Approved |
IVRS - Inspection :* |
| 05/14/2004 |
FRAMING |
|
Partial Approval |
IVRS - Inspection :*/ 1) FAMILY ROOM ADDITION-GARAGE NOT READY 2) BASE BOARD ELECTRIC HEATERS MUST BE HARD WIRED AND ON A DEDICATED CIRCUIT 3) MAKE UP (CONNECT) ALL GROUND WIRES IN ELECTRIC BOXES AND SECURE WITH MECHANICAL FASTENER. PROVIDE A SEPERATE GROUND PIG TAIL FOR EACH SWITCH AND OUTLET 4) GROUND ALL METAL ELECTRIC BOXES 5) ALL JUNCTION BOXES MUST BE ACCESSIBLE AFTER DRYWALL IS INSTALLED 6) DRYWALL SCREWS NOT ALLOWED TO SECURE FAN BOX. USE #10 WOOD OR METAL SCREWS |