Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T04CM01587
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/01/2004 | FRAMING | Approved | IVRS - Inspection :* | |
06/30/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) LUS48 HANGER MISSING ?? AT GARAGE |
|
06/25/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SAME 2 PREVIOUS INSPECTION 2) REFEE DUE PRIOR TO REINSPECTION COMPLY WITH #2, 3, 4 AND 9 OF REJ. DATED 6/23/04 |
|
06/24/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) COMPLY WITH #2, 3, 4 AND 9 OF PREVIOUS INSPECTION |
|
06/23/2004 | FRAMING | Not ready for Inspection | IVRS - Inspection :*/ 1) HAVE ROOF NAIL ENTERED IN IVR SYSTEM 2) PLAN CALLS FOR LUS48 HANGERS IN GARAGE AT TRUSS TO GIRDER PAGE S2.1/S2.1 3) SHIM 3 PT BEARING AT GARAGE INTERIOR 4) PEX 12" TO CAN LIGHT KITCHEN CEILING 5) CANNOT HAVE OUTLET BELOW COUNTER OVER HANG, UNLESS UNDER 6" CANTILEVER THEN ? TO BE 6" FROM HORIZONTAL TOP OF COUNTER 6) 2ND FLOOR DECKING MISSING NAILING THRU OUT 7) GAS TEST NOT HOLDING 8) POTABLE WATER/DWV OK 9) NEED A/BOLT AT FRONT DOOR SILL 10) NAIL BOTTOM PLATES 2ND FLOOR |