Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2004 | FRAMING | Approved | IVRS - Inspection :* | |
| 07/01/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PROVIDE 60 DEGREE PITCH AT B-VENT 2) FRAMING WILL BE APPROVED WHEN ALL TRADES HAVE BEEN APPROVED 3) AIR TEST ON WATER LINE FAILED |
|
| 06/28/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) SEAL ALL PENETRATIONS FROM 1ST TO 2ND FLOOR AND INTO ATTIC 2) FRAMING WILL BE APPROVED WHEN ALL TRADES ARE COMPLETE 3) SEAL PENETRATIONS REAR OF HOUSE 4) NO TRENCH 5) TAPE EXPOSED HOT ENDS AND 6) MOVE AWAY FROM BUZZ BAR 7) NO TEST ON DWV'S 8) NO TEST ON WATER LINES 9) NAIL PROTECT COPPER LINE IN GARAGE 10) NAIL PROTECT ALL PLUMBING WITHIN 1 1\2" FROM EDGE OF STUD |
|
| 06/24/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) ELECTRICAL WIRE HANGING IN GARAGE 2) HOT LEADS TOUCHING BUZZ BAR AND EXPOSED 3) NO TEST ON DWV'S OR WATER LINES 4) STOPPED INSPECTION |