Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/14/2005 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 04/07/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) KITCHEN COUNTER TOP OUTLETS TO BE NO FURTHER APART THAN 48" 2) OPEN GROUND KITCHEN GFCI 3) PAINT EXPOSED PLUMBING VENTS ON ROOF 4) INSTALL FIREPLACES DAMPER DEVICE SO AS NOT TO CLOSE ALL THE WAY 5) FIREPLACE FACE NEXT TO OPENING EXCEEDS ALLOWABLE LIMITS (SEE SPECS) 6) HANDRAIL TO BE BETWEEN 34"-38" 7) INSTALL NON-COMBUSTIBLE HEARTH FIREPLACE 8) STAIR LIGHT FIXTURES TO BE MINIMUM 6'-8" ABOVE STAIR TREAD |
|
| 04/01/2005 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CAULK AROUND BASE OF TOILETS 2) WHAT IS 220 BOXES GARAGE FOR ? (ELECTRIC) 3) COMPLETE ELECTRIC GARAGE 4) WHAT IS ELECTRIC DISCONNECT EAST SIDE EXTERIOR HOUSE FOR ? 5) ELECTRIC DISCONNECT CANNOT BE BEHIND A/C UNITS 6) GARAGE OUTLETS TO BE GFCI PROTECTED 7) COMPLETE GRADING 8) INSTALL BONDING JUMPER ACCROSS NON METALLIC A/C BELLOWS 9) PAINT EXTERIOR 10) COMPLETE CONCRETE DRIVES 11) INSTALL LIGHT MECH ROOM 12) ELECTRIC TO HEATER (H2D) 13) STOPPED INSPECTION |