Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/07/2004 | ELECTRIC - INTERMEDIATE | Approved | ||
| 04/27/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) GFCI OUTLET REQUIRED IN BATHROOM 2) INSTALL ELECTRICAL OUTLETS AS SHOWN ON PLAN 3) EXPOSED ROMEX NOT PERMITTED BELOW 6'-8" 4) PLUMBING VENTS MUST EXTEND ABOVE ROOF 5) SINK DRAIN NOT VENTED PER CODE (COULD USE AIR ADMITTANCE VALVE) 6) UNVENTED GAS HEATERS NOT PERMITTED IN LIVING SPACE 7) INSTALL SMOKE DETECTORS |
|
| 04/26/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : There is no plan or job inspection card on site.| 925* |